ESTIMATED HYDROGEN EMISSION

 

HYDROGEN GENERATED DURING CHARGING:

MAX CFM HYDROGEN GENERATED = 0.00027(CHARGE AMPS)(NUMBER OF CELLS IN SERIES)

60 A charge rate = 0.39 CFM

50 A charge rate = 0.32 CFM

40 A charge rate = 0.26 CFM

30 A charge rate = 0.20 CFM

20 A charge rate = 0.13 CFM

 

AIR REQUIRED FOR 2% MAX HYDROGEN CONCENTRATION:

MIN CFM VENTILATION REQUIRED = 0.0135(CHARGE AMPS)(NUMBER OF CELLS IN SERIES)

60 A charge rate = 19.4 CFM

50 A charge rate = 16.2 CFM

40 A charge rate = 13 CFM

30 A charge rate = 9.7 CFM

20 A charge rate = 6.5 CFM

 